{"id":354,"date":"2016-12-28T10:22:52","date_gmt":"2016-12-28T15:22:52","guid":{"rendered":"http:\/\/www.mroelectric.com\/blog\/?p=354"},"modified":"2019-06-26T10:44:10","modified_gmt":"2019-06-26T14:44:10","slug":"micromaster-420-troubleshooting","status":"publish","type":"post","link":"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/","title":{"rendered":"Siemens Micromaster 420 Troubleshooting Tips"},"content":{"rendered":"<p>Often people have difficulty installing a replacement drive that we send out, and normally it just takes the troubleshooting tips from the manual to get them up and running. However, the manual isn&#8217;t always the easiest to find or sort through, so below we&#8217;re posting the <a href=\"https:\/\/www.mroelectric.com\/siemens\/1\">Siemens<\/a> Micromaster 420 Troubleshooting section from the manual which should help anyone who is working to get the issues with their drive sorted out.<\/p>\n<h5>MRO Electric supplies and repairs <a href=\"https:\/\/www.mroelectric.com\/siemens\/micromaster\/1\">Micromaster 420 Drives<\/a>. To request a quote for a repair or spare, please call 800-691-8511 or email <a href=\"mailto:sales@mroelectric.com\">sales@mroelectric.com<\/a>.<\/h5>\n<p><!--more--><\/p>\n<p><b>Troubleshooting with the BOP<\/b><\/p>\n<p>Warnings and faults displayed on the BOP with Axxx and Fxxx respectively. The individual messages are shown in the Parameter list.<\/p>\n<p>If the motor fails to start when the ON command has been given<\/p>\n<p>&#8211;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp; Check that P0010 = 0<\/p>\n<p>&#8211;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp; Check that a valid ON signal is present<\/p>\n<p>&#8211;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp; Check that P0700 = 2 (for digital input control) or P0700 = 1 (for BOP control)<\/p>\n<p>&#8211;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp; Check that the setpoint is present (0 to 10V on Terminal 3) or the setpoint has been entered into the correct parameter, depending on the setpoint source (P1000). Se the Parameter List for further details.<\/p>\n<p>If the motor fails to run after changing the parameters, set P0010 = 30 then P0970 = 1 and press P to reset the inverter to the factory default parameter values.<\/p>\n<p>Now use a switch between terminals 5 and 8 on the control board. The drive should now run to the defined setpoint by analogue input.<\/p>\n<p><b>Fault Messages<\/b><\/p>\n<p>In the event of a failure, the inverter switches off and a fault code appears on the display.<\/p>\n<p>NOTE<\/p>\n<p>To reset the fault code, one of three methods listed below can be used:<\/p>\n<p>1. Cycle the power to the drive.<\/p>\n<p>2. Press the&nbsp; button on the BOP or AOP.<\/p>\n<p>3. Via Digital Input 3 (default setting)<\/p>\n<p>Fault messages are stored in parameter r0947 under their code number (e.g. F0003 = 3). The associated error value is found in parameter r0949. The value 0 is entered if a fault has no error value. It is furthermore possible to read out the point in time that a fault occurred (r0948) and the number of fault messages (P0952) stored in Parameter r0947.<\/p>\n<p>A detailed description of the fault messages is provided in the parameter list.<\/p>\n<p><b>Alarm Messages<\/b><\/p>\n<p>Alarm messages are stored in parameter r2110 under their code number (e.g. A0503 = 503) and can be read out from there.&nbsp; A detailed description of the alarm messages is provided in the parameter list.<\/p>\n<p><b>Suppressing Fault\/Alarm Messages<\/b><\/p>\n<p>From the perspective of the application and user, fault-free operation is the decisive criterion when it comes to the acceptance of drive systems. For special applications, not only this, but fault-free operation is required even if an overload condition exists or external events cause faults. For applications such as these (e.g. mixer systems), fault-free operation has a higher priority than the protection of the drive system.<\/p>\n<p>With MICROMASTER, it is possible to suppress up to 3 fault \/ alarm messages using the indexed parameters P2100 and P2101. The fault \/ alarm messages to be suppressed (refer to Section &#8220;Fault \/ alarm messages&#8221;) are selected using parameter P2100 while the response is entered using parameter P2101. Indices 0 &#8211; 2 of the two parameters are used to correlate between suppressing the fault \/ alarm messages and the response. The following settings are possible for the responses:<\/p>\n<p>0 No response, no display<\/p>\n<p>1 OFF1 stop response<\/p>\n<p>2 OFF2 stop response<\/p>\n<p>3 OFF3 stop response<\/p>\n<p>4 No response, only a warning<\/p>\n<p><b>Example<\/b>: Alarm A0911 indicates that the drive has extended the ramp run-down time in order to avoid an overvoltage condition. If you wish to suppress this message, then set the following parameters: P2100[0] = 911 (selects Alarm A0911) P2101[0] = 0&nbsp; (no response, no display)<\/p>\n<p><b>NOTE<\/b>&nbsp; All of the fault messages are assigned the standard response to OFF2 (refer to the fault\/alarm list).&nbsp; The standard responses of several fault messages, caused by the hardware &#8211; e.g. overcurrent F0001 &#8211; can neither be suppressed nor modified.<\/p>\n<figure id=\"attachment_1286\" class=\"thumbnail wp-caption alignnone\" style=\"width: 2305px\"><img loading=\"lazy\" decoding=\"async\" class=\"size-full wp-image-1286\" src=\"https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/2015\/08\/Micromaster.jpg\" alt=\"Micromaster 420\" width=\"2295\" height=\"1909\" srcset=\"https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/2015\/08\/Micromaster.jpg 2295w, https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/2015\/08\/Micromaster-300x250.jpg 300w, https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/2015\/08\/Micromaster-768x639.jpg 768w, https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/2015\/08\/Micromaster-1024x852.jpg 1024w\" sizes=\"auto, (max-width: 2295px) 100vw, 2295px\" \/><figcaption class=\"caption wp-caption-text\">Micromaster 420<\/figcaption><\/figure>\n\n\n<div class=\"wp-block-image\"><figure class=\"aligncenter\"><img loading=\"lazy\" decoding=\"async\" width=\"1024\" height=\"852\" src=\"https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/micromaster-1-1024x852.jpg\" alt=\"\" class=\"wp-image-3955\" srcset=\"https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/micromaster-1-1024x852.jpg 1024w, https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/micromaster-1-300x250.jpg 300w, https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/micromaster-1-768x639.jpg 768w\" sizes=\"auto, (max-width: 1024px) 100vw, 1024px\" \/><\/figure><\/div>\n","protected":false},"excerpt":{"rendered":"<p>Often people have difficulty installing a replacement drive that we send out, and normally it just takes the troubleshooting tips from the manual to get them up and running. However, the manual isn&#8217;t always the easiest to find or sort through, so below we&#8217;re posting the Siemens Micromaster 420 Troubleshooting section from the manual which [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":1677,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_lmt_disableupdate":"","_lmt_disable":"","_exactmetrics_skip_tracking":false,"_exactmetrics_sitenote_active":false,"_exactmetrics_sitenote_note":"","_exactmetrics_sitenote_category":0,"ngg_post_thumbnail":0,"footnotes":""},"categories":[235,12],"tags":[88],"class_list":["post-354","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-siemens","category-troubleshooting-and-repair","tag-micromaster"],"yoast_head":"<!-- This site is optimized with the Yoast SEO Premium plugin v25.3.1 (Yoast SEO v25.3.1) - https:\/\/yoast.com\/wordpress\/plugins\/seo\/ -->\n<title>Siemens Micromaster 420 Drive - Troubleshooting Tips<\/title>\n<meta name=\"description\" content=\"Some helpful tips on Siemens Micromaster 420 troubleshooting from the appropriate section in the manual. We carry new and refurbished Micromaster 420 Drives\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/\" \/>\n<meta property=\"og:locale\" content=\"en_US\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Siemens Micromaster 420 Troubleshooting Tips\" \/>\n<meta property=\"og:description\" content=\"Some helpful tips on Siemens Micromaster 420 troubleshooting from the appropriate section in the manual. We carry new and refurbished Micromaster 420 Drives\" \/>\n<meta property=\"og:url\" content=\"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/\" \/>\n<meta property=\"og:site_name\" content=\"MRO Electric Blog\" \/>\n<meta property=\"article:publisher\" content=\"https:\/\/www.facebook.com\/mroelectric\/\" \/>\n<meta property=\"article:published_time\" content=\"2016-12-28T15:22:52+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2019-06-26T14:44:10+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/2017\/02\/micromaster.jpg\" \/>\n\t<meta property=\"og:image:width\" content=\"2295\" \/>\n\t<meta property=\"og:image:height\" content=\"1909\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/jpeg\" \/>\n<meta name=\"author\" content=\"Joe Kaminski\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:creator\" content=\"@mroelectric\" \/>\n<meta name=\"twitter:site\" content=\"@mroelectric\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"Joe Kaminski\" \/>\n\t<meta name=\"twitter:label2\" content=\"Est. reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"3 minutes\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\/\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/#article\",\"isPartOf\":{\"@id\":\"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/\"},\"author\":{\"name\":\"Joe Kaminski\",\"@id\":\"https:\/\/www.mroelectric.com\/blog\/#\/schema\/person\/b993515a2417163a23dfe88597c8d13a\"},\"headline\":\"Siemens Micromaster 420 Troubleshooting Tips\",\"datePublished\":\"2016-12-28T15:22:52+00:00\",\"dateModified\":\"2019-06-26T14:44:10+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/\"},\"wordCount\":705,\"commentCount\":5,\"publisher\":{\"@id\":\"https:\/\/www.mroelectric.com\/blog\/#organization\"},\"image\":{\"@id\":\"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/2017\/02\/micromaster.jpg\",\"keywords\":[\"Micromaster\"],\"articleSection\":[\"Siemens\",\"Troubleshooting &amp; Repair\"],\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/\",\"url\":\"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/\",\"name\":\"Siemens Micromaster 420 Drive - Troubleshooting Tips\",\"isPartOf\":{\"@id\":\"https:\/\/www.mroelectric.com\/blog\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/#primaryimage\"},\"image\":{\"@id\":\"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/2017\/02\/micromaster.jpg\",\"datePublished\":\"2016-12-28T15:22:52+00:00\",\"dateModified\":\"2019-06-26T14:44:10+00:00\",\"description\":\"Some helpful tips on Siemens Micromaster 420 troubleshooting from the appropriate section in the manual. We carry new and refurbished Micromaster 420 Drives\",\"breadcrumb\":{\"@id\":\"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/#breadcrumb\"},\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/#primaryimage\",\"url\":\"https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/2017\/02\/micromaster.jpg\",\"contentUrl\":\"https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/2017\/02\/micromaster.jpg\",\"width\":2295,\"height\":1909,\"caption\":\"Micromaster 420\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\/\/www.mroelectric.com\/blog\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Siemens Micromaster 420 Troubleshooting Tips\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\/\/www.mroelectric.com\/blog\/#website\",\"url\":\"https:\/\/www.mroelectric.com\/blog\/\",\"name\":\"MRO Electric Blog\",\"description\":\"Applications of PLCs, CNCs, and more!\",\"publisher\":{\"@id\":\"https:\/\/www.mroelectric.com\/blog\/#organization\"},\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\/\/www.mroelectric.com\/blog\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-US\"},{\"@type\":\"Organization\",\"@id\":\"https:\/\/www.mroelectric.com\/blog\/#organization\",\"name\":\"MRO Electric and Supply\",\"url\":\"https:\/\/www.mroelectric.com\/blog\/\",\"logo\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\/\/www.mroelectric.com\/blog\/#\/schema\/logo\/image\/\",\"url\":\"https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/mro-logo-new_large2_blue-1.png\",\"contentUrl\":\"https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/mro-logo-new_large2_blue-1.png\",\"width\":430,\"height\":222,\"caption\":\"MRO Electric and Supply\"},\"image\":{\"@id\":\"https:\/\/www.mroelectric.com\/blog\/#\/schema\/logo\/image\/\"},\"sameAs\":[\"https:\/\/www.facebook.com\/mroelectric\/\",\"https:\/\/x.com\/mroelectric\"]},{\"@type\":\"Person\",\"@id\":\"https:\/\/www.mroelectric.com\/blog\/#\/schema\/person\/b993515a2417163a23dfe88597c8d13a\",\"name\":\"Joe Kaminski\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\/\/www.mroelectric.com\/blog\/#\/schema\/person\/image\/\",\"url\":\"https:\/\/secure.gravatar.com\/avatar\/fb7c0d641ed541ad912b27609e8079304fc356be7b5b53578b32ad3fa973f506?s=96&d=mm&r=g\",\"contentUrl\":\"https:\/\/secure.gravatar.com\/avatar\/fb7c0d641ed541ad912b27609e8079304fc356be7b5b53578b32ad3fa973f506?s=96&d=mm&r=g\",\"caption\":\"Joe Kaminski\"},\"description\":\"Joe Kaminski is an industrial automation specialist at MRO Electric. He has a background in industrial engineering and supply chain management. Joe has worked in the automation industry for over 10 years providing support to some of the largest companies in the world. For more info, visit www.mroelectric.com.\",\"url\":\"https:\/\/www.mroelectric.com\/blog\/author\/jadmin\/\"}]}<\/script>\n<!-- \/ Yoast SEO Premium plugin. -->","yoast_head_json":{"title":"Siemens Micromaster 420 Drive - Troubleshooting Tips","description":"Some helpful tips on Siemens Micromaster 420 troubleshooting from the appropriate section in the manual. We carry new and refurbished Micromaster 420 Drives","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/","og_locale":"en_US","og_type":"article","og_title":"Siemens Micromaster 420 Troubleshooting Tips","og_description":"Some helpful tips on Siemens Micromaster 420 troubleshooting from the appropriate section in the manual. We carry new and refurbished Micromaster 420 Drives","og_url":"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/","og_site_name":"MRO Electric Blog","article_publisher":"https:\/\/www.facebook.com\/mroelectric\/","article_published_time":"2016-12-28T15:22:52+00:00","article_modified_time":"2019-06-26T14:44:10+00:00","og_image":[{"width":2295,"height":1909,"url":"https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/2017\/02\/micromaster.jpg","type":"image\/jpeg"}],"author":"Joe Kaminski","twitter_card":"summary_large_image","twitter_creator":"@mroelectric","twitter_site":"@mroelectric","twitter_misc":{"Written by":"Joe Kaminski","Est. reading time":"3 minutes"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/#article","isPartOf":{"@id":"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/"},"author":{"name":"Joe Kaminski","@id":"https:\/\/www.mroelectric.com\/blog\/#\/schema\/person\/b993515a2417163a23dfe88597c8d13a"},"headline":"Siemens Micromaster 420 Troubleshooting Tips","datePublished":"2016-12-28T15:22:52+00:00","dateModified":"2019-06-26T14:44:10+00:00","mainEntityOfPage":{"@id":"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/"},"wordCount":705,"commentCount":5,"publisher":{"@id":"https:\/\/www.mroelectric.com\/blog\/#organization"},"image":{"@id":"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/#primaryimage"},"thumbnailUrl":"https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/2017\/02\/micromaster.jpg","keywords":["Micromaster"],"articleSection":["Siemens","Troubleshooting &amp; Repair"],"inLanguage":"en-US","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/#respond"]}]},{"@type":"WebPage","@id":"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/","url":"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/","name":"Siemens Micromaster 420 Drive - Troubleshooting Tips","isPartOf":{"@id":"https:\/\/www.mroelectric.com\/blog\/#website"},"primaryImageOfPage":{"@id":"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/#primaryimage"},"image":{"@id":"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/#primaryimage"},"thumbnailUrl":"https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/2017\/02\/micromaster.jpg","datePublished":"2016-12-28T15:22:52+00:00","dateModified":"2019-06-26T14:44:10+00:00","description":"Some helpful tips on Siemens Micromaster 420 troubleshooting from the appropriate section in the manual. We carry new and refurbished Micromaster 420 Drives","breadcrumb":{"@id":"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/#breadcrumb"},"inLanguage":"en-US","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/"]}]},{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/#primaryimage","url":"https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/2017\/02\/micromaster.jpg","contentUrl":"https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/2017\/02\/micromaster.jpg","width":2295,"height":1909,"caption":"Micromaster 420"},{"@type":"BreadcrumbList","@id":"https:\/\/www.mroelectric.com\/blog\/micromaster-420-troubleshooting\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/www.mroelectric.com\/blog\/"},{"@type":"ListItem","position":2,"name":"Siemens Micromaster 420 Troubleshooting Tips"}]},{"@type":"WebSite","@id":"https:\/\/www.mroelectric.com\/blog\/#website","url":"https:\/\/www.mroelectric.com\/blog\/","name":"MRO Electric Blog","description":"Applications of PLCs, CNCs, and more!","publisher":{"@id":"https:\/\/www.mroelectric.com\/blog\/#organization"},"potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.mroelectric.com\/blog\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-US"},{"@type":"Organization","@id":"https:\/\/www.mroelectric.com\/blog\/#organization","name":"MRO Electric and Supply","url":"https:\/\/www.mroelectric.com\/blog\/","logo":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/www.mroelectric.com\/blog\/#\/schema\/logo\/image\/","url":"https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/mro-logo-new_large2_blue-1.png","contentUrl":"https:\/\/www.mroelectric.com\/blog\/wp-content\/uploads\/mro-logo-new_large2_blue-1.png","width":430,"height":222,"caption":"MRO Electric and Supply"},"image":{"@id":"https:\/\/www.mroelectric.com\/blog\/#\/schema\/logo\/image\/"},"sameAs":["https:\/\/www.facebook.com\/mroelectric\/","https:\/\/x.com\/mroelectric"]},{"@type":"Person","@id":"https:\/\/www.mroelectric.com\/blog\/#\/schema\/person\/b993515a2417163a23dfe88597c8d13a","name":"Joe Kaminski","image":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/www.mroelectric.com\/blog\/#\/schema\/person\/image\/","url":"https:\/\/secure.gravatar.com\/avatar\/fb7c0d641ed541ad912b27609e8079304fc356be7b5b53578b32ad3fa973f506?s=96&d=mm&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/fb7c0d641ed541ad912b27609e8079304fc356be7b5b53578b32ad3fa973f506?s=96&d=mm&r=g","caption":"Joe Kaminski"},"description":"Joe Kaminski is an industrial automation specialist at MRO Electric. He has a background in industrial engineering and supply chain management. Joe has worked in the automation industry for over 10 years providing support to some of the largest companies in the world. For more info, visit www.mroelectric.com.","url":"https:\/\/www.mroelectric.com\/blog\/author\/jadmin\/"}]}},"modified_by":"Ryan Dickinson","_links":{"self":[{"href":"https:\/\/www.mroelectric.com\/blog\/wp-json\/wp\/v2\/posts\/354","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.mroelectric.com\/blog\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.mroelectric.com\/blog\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.mroelectric.com\/blog\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/www.mroelectric.com\/blog\/wp-json\/wp\/v2\/comments?post=354"}],"version-history":[{"count":7,"href":"https:\/\/www.mroelectric.com\/blog\/wp-json\/wp\/v2\/posts\/354\/revisions"}],"predecessor-version":[{"id":3956,"href":"https:\/\/www.mroelectric.com\/blog\/wp-json\/wp\/v2\/posts\/354\/revisions\/3956"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.mroelectric.com\/blog\/wp-json\/wp\/v2\/media\/1677"}],"wp:attachment":[{"href":"https:\/\/www.mroelectric.com\/blog\/wp-json\/wp\/v2\/media?parent=354"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.mroelectric.com\/blog\/wp-json\/wp\/v2\/categories?post=354"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.mroelectric.com\/blog\/wp-json\/wp\/v2\/tags?post=354"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}